600KVA off grid three phase inverter technical parameters
Type | NB480-600KSZ | |
DC input | Input rated voltage | 480 VDC |
Input rated current | 1250 A | |
Input DC voltage range | 400-600 VDC | |
AC input (AC Bypass) | Allow input voltage range | 220 VAC / 380 VAC / 400 VAC ± 15% VAC |
Input rated current | 1550A / 910A / 870A | |
Bypass transfer time | ≤4 ms | |
AC output | Rated capacity | 600KVA |
Output rated power | 480KW | |
Output rated voltage and frequency | 220 VAC / 380 VAC / 400 VAC ,50Hz / 60Hz | |
Output rated current | 1550A / 910A / 870A | |
Output voltage accuracy | 220 VAC / 380 VAC / 400 VAC ± 2% | |
Output frequency accuracy | 50Hz / 60Hz ±0.05% | |
Waveform distortion (THD). | ≤3% | |
Dynamic response time | 2ms | |
Power factor (PF) | 0.8 | |
Overload capacity | 120%,3 minutes,150%,10 second | |
Crest factor (CF) | 3:1 | |
Inverter efficiency | 96% | |
Working Environment | Dielectric strength | 1500VAC,1minute |
Noise (1m) | ≤50dB | |
Ambient temperature | -10℃~+50℃ | |
Humidity | 0~90%,No condensation | |
Altitude | ≤5000 m | |
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | |
Equipped with copper transformer | Yes | |
Pure Sine Wave | Yes | |
AC Charger | Optional | |
Solar Charger | Optional | |
Generator port | Optional | |
Product Size | 1910*1160*1880mm | |
Product Weight | 1800kg |