50KVA off grid single phase inverter technical parameters
Type | NB220-50KDZ | NB380-50KDZ | ||
DC input | Input rated voltage | 220 VDC | 380 VDC | |
Input rated current | 227 A | 132 A | ||
Input DC voltage range | 180-300 VDC | 300-490VDC | ||
AC input (AC Bypass) | Allow input voltage range | 110VAC/120VAC/220VAC/240VAC ± 15% VAC | ||
Input rated current | 455A / 417A / 227A /208A | |||
Bypass transfer time | ≤4 ms | |||
AC output | Rated capacity | 50KVA | ||
Output rated power | 40KW | |||
Output rated voltage and frequency | 110VAC/120VAC/220VAC/240VAC,50Hz / 60Hz | |||
Output rated current | 455A / 417A / 227A / 208A | |||
Output voltage accuracy | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 2% | |||
Output frequency accuracy | 50Hz / 60Hz ±0.05% | |||
Waveform distortion (THD). | ≤3% | |||
Dynamic response time | 5% | |||
Power factor (PF) | 0.8 | |||
Overload capacity | 120%,3 minutes,150%,10 second | |||
Crest factor (CF) | 3:1 | |||
Inverter efficiency | 90% | |||
Working Environment | Dielectric strength | 1500VAC,1minute | ||
Noise (1m) | ≤50dB | |||
Ambient temperature | -10℃~+50℃ | |||
Humidity | 0~90%, No condensation | |||
Altitude | ≤5000 m | |||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | |||
Equipped with isolated transformer | Yes | |||
Pure Sine Wave | Yes | |||
AC Charger | Available, optional | |||
Solar Battery Charger | Available, optional | |||
Dry Contact | Available. optional | |||
Size(mm) | 660*1300*1600mm | |||
Weight(kg) | 510kg |
62.5KVA (50KW) Off Grid Single Phase Inverter Technical Data Sheet
Type | NB220-62.5KDZ | NB380-62.5KDZ | |
DC input | Input rated voltage | 220 VDC | 380 VDC |
Input rated current | 284 A | 165 A | |
Input DC voltage range | 180-300 VDC | 300-490VDC | |
AC input (AC Bypass) | Allow input voltage range | 110VAC/120VAC/220VAC/240VAC ± 15%VAC | |
Input rated current | 569A /521A /284A /260A | ||
Bypass transfer time | ≤4 ms | ||
AC output | Rated capacity | 62.5KVA | |
Output rated power | 50KW | ||
Output rated voltage and frequency | 110VAC/120VAC/220VAC/240VAC, 50Hz/60Hz | ||
Output rated current | 455A/417A/227A/208A | ||
Output voltage accuracy | 110VAC/120VAC/220VAC/240VAC ± 2% | ||
Output frequency accuracy | 50Hz / 60Hz ±0.05% | ||
Waveform distortion (THD).(Linear load) | ≤3% | ||
Dynamic response time | 5% | ||
Power factor (PF) | 0.8 | ||
Overload capacity | 120%,3minutes,150%,10second | ||
Crest factor (CF) | 3:1 | ||
Inverter efficiency | 90% | ||
Working Environment | Dielectric strength | 1500VAC,1minute | |
Noise (1m) | ≤50dB | ||
Ambient temperature | -10℃~+50℃ | ||
Humidity | 0~90%, No condensation | ||
Altitude | ≤5000 m | ||
Pure Sine Wave | Yes | ||
Equipped with copper transformer | Yes | ||
If solar charger is available | Yes | ||
AC Charger | Available, optional | ||
Dry Contact | Available. optional | ||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | ||
Size(mm) | 660*1300*1600mm | ||
Weight(kg) | 510kg |