30KVA off grid single phase inverter technical parameters
Type | NB110- 30KDZ | NB220- 30KDZ | NB380- 30KDZ | |
DC input | Input rated voltage | 110 VDC | 220 VDC | 380 VDC |
Input rated current | 273A | 136 A | 79 A | |
Input DC voltage range | 75-135 VDC | 180-300 VDC | 300-490VDC | |
AC input (AC Bypass) | Allow input voltage range | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 15% VAC | ||
Input rated current | 272A / 250A / 136 A /125A | |||
Bypass transfer time | ≤4 ms | |||
AC output | Rated capacity | 30KVA | ||
Output rated power | 24KW | |||
Output rated voltage and frequency | 110VAC/120VAC/220VAC/240VAC,50Hz/60Hz | |||
Output rated current | 272A / 250A / 136 A /125A | |||
Output voltage accuracy | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 2% | |||
Output frequency accuracy | 50Hz / 60Hz ±0.05% | |||
Waveform distortion (THD).(Linear load) | ≤3% | |||
Dynamic response time | 5% | |||
Power factor (PF) | 0.8 | |||
Overload capacity | 120%,3 minutes,150%,10 second | |||
Crest factor (CF) | 3:1 | |||
Inverter efficiency | 90% | |||
Working Environment | Dielectric strength | 1500VAC,1minute | ||
Noise (1m) | ≤50dB | |||
Ambient temperature | -10℃~+50℃ | |||
Humidity | 0~90%, No condensation | |||
Altitude | ≤5000 m | |||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | |||
Equipped with isolated transformer | Yes | |||
Pure Sine Wave | Yes | |||
AC Charger | Available, optional | |||
Solar Battery Charger | Available, optional | |||
Dry Contact | Available. optional | |||
Size(mm) | 800*600*2260mm | |||
Weight(kg) | 360kg |
40KVA (32KW) Off Grid Single Phase Inverter Technical Data Sheet
Type | NB192- 40KDZ | NB240- 40KDZ | NB380- 40KDZ | |
DC input | Input rated voltage | 192 VDC | 240VDC | 380 VDC |
Input rated current | 208 A | 166 A | 104 A | |
Input DC voltage range | 160-270 VDC | 200-335 VDC | 300-490VDC | |
AC input (AC Bypass) | Allow input voltage range | 110VAC/120VAC/220VAC/240VAC ± 15% VAC | ||
Input rated current | 364A / 334A / 182A / 166A | |||
Bypass transfer time | ≤4 ms | |||
AC output | Rated capacity | 40KVA | ||
Output rated power | 32KW | |||
Output rated voltage and frequency | 110VAC/120VAC/220VAC /240VAC,50Hz/60Hz | |||
Output rated current | 364A /334A /182A /166A | |||
Output voltage accuracy | 110VA /120 VAC / 220 VAC / 240 VAC ± 2% | |||
Output frequency accuracy | 50Hz / 60Hz ±0.05% | |||
Waveform distortion (THD).(Linear load) | ≤3% | |||
Dynamic response time | 5% | |||
Power factor (PF) | 0.8 | |||
Overload capacity | 120%,3minutes,150%,10second | |||
Crest factor (CF) | 3:1 | |||
Inverter efficiency | 92% | |||
Working Environment | Dielectric strength | 1500VAC,1minute | ||
Noise (1m) | ≤50Db | |||
Ambient temperature | -10℃~+50℃ | |||
Humidity | 0~90%, No condensation | |||
Altitude | ≤5000 m | |||
Pure Sine Wave | Yes | |||
Equipped with copper transformer | Yes | |||
If solar charger is available | Yes | |||
AC Charger | Optional | |||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | |||
Size(mm) | ||||
Weight(kg) | 510kg |